IEWC.com

Trimm Inc. GMT Fuse Panels


GMT FUSE PANEL 20A -/+24 TO 48V DC

  • 10/10 GMT panel
  • 125A per bus
  • 20A GMT positions
  • Ambient rating up to +65° C, making them suitable for outside plant cabinets
  • Made in the USA
GENERAL

Dimensions:

19.00" W x 1.75" H x 11.250" D
Rack Space: 1U
Weight: 5.5 lbs.
Mounting: Universal 19" or 23", WECO or EIA
Mtg. Pos.: Flush, 4" or 5" Offset
Finish: Black Textured Powder Coat

ELECTRICAL
Input: Nominal Voltage: -/+24-48V DC
Voltage Range: -/+19-60V DC
Number of Buses: 2
Intr. Device Rating: 150 Amps
Output: Max Fuse Rating: 20 Amp
Continuous Load Rating: 16 Amps

ALARMING
Indicators: Green (Power)/ Red (Alarm)
Function: Form C relay contacts for remote fuse and power fail indication
Conn. Type: Solderless Wire Wrap (18 to 30 AWG)
Rating: DC 30W/AC 50VA

STANDARDS
Safety (Listed): UL 60950-1/UL 1801/CSA C22.2
No.60950-1/EN 60950-1/IEC 60950-1
Telcordia: NEBS Level 3 (GR-63/GR-1089) and
GR-3108 Class 3 (w/o salt fog testing)

ENVIRONMENT
Short Term Op Temp: -40° C to +70° C
Ambient: Up to 65° C
Store Temp: -40° C to +70° C
Humidity: 0 to 95% non-condensing
Power Dissipation: 49.25 Watts max

CONNECTIONS
Input: 2 Hole Lug: 1/4" stud x 5/8" spacing
Wire Range: Up to 2/0 AWG
Max. Terminal Width: 0.640"
Tightening Torque: 40 in-lb (4.5 Nm)
Output: Barrier Strip Output: #6 Sems Screw for Terminals
Wire Range:  10 to 22 AWG
Max. Terminal Width: 0.312"
Tightening Torque: 10 in-lb (1.1 Nm)
Ground Bus: 2 Hole Lug: 1/4" stud x 1" spacing
Wire Range:  6 AWG lug supplied with panel

54080